Drinking Water Treatment with UV Irradiation


Ultraviolet (UV) rays are part of the light that comes from the sun. The UV spectrum is higher in frequency than visible light and lower in frequency compared to  x-rays. This also means that the UV spectrum has a larger wavelength than x-rays and a smaller wavelength than visible light and the order of energy, from low to high, is visible light, UV, than x-rays. As a water treatment technique, UV is known to be an effective disinfectant due to its strong germicidal (inactivating) ability. UV disinfects water containing bacteria and viruses and can be effective against protozoans like,  Giardia lamblia cysts or Cryptosporidium oocysts. UV has been used commercially for many years in the pharmaceutical, cosmetic, beverage, and electronics industries, especially in Europe. In the US, it was used for drinking water disinfection and treatment in the early 1900s but was abandoned due to high operating costs, unreliable equipment, and the expanding popularity of disinfection by chlorination. 

Because of safety issues associated with the reliance of chlorination and improvement in the UV technology, UV has experienced increased acceptance in both municipal and household drinking water treatment systems. There are few large-scale UV water treatment plants in the United States although there are more than 2,000 such plants in Europe.  There are two classes of disinfection systems certified and classified by the NSF under Standard 55 – Class A and Class B Units.

Class A — These ultraviolet water treatment systems must have an ‘intensity & saturation’ rating of at least 40,000 uwsec/cm2 and possess designs that will allow them to disinfect and/or remove microorganisms from contaminated water. Affected contaminants should include bacteria and viruses  
"Class A point-of-entry and point-of-use systems covered by this Standard are designed to inactivate and/or remove microorganisms, including bacteria, viruses, Cryptosporidium oocyst and Giardia cysts, from contaminated water. Systems covered by this standard are not intended for the treatment of water that has obvious contamination or intentional source such as raw sewage, nor are systems intended to convert wastewater to drinking water. The systems are intended to be installed on visually clear water."

Class B — These ultraviolet water treatment systems must have an ‘intensity & saturation’ rating of at least 16,000 uw-sec/cm2 and possess designs that will allow them to provide supplemental bactericidal treatment of water already deemed ‘safe’. i.e., no elevated levels of E. coli. or a standard plate count of less than 500 colonies per 1 ml.  NSF Standard 55 "Class B" UV systems are designed to operate at a minimum dosage and are intended to "reduce normally occurring non-pathogenic or nuisance microorganisms only." The "Class B" or similar non-rated UV systems are not intended for the disinfection of "microbiologically unsafe water."

Therefore, the type of unit depends on your situation, source of water, and your drinking water quality. Transmitted UV light dosage is affected by water clarity. Drinking water treatment devices are dependent on the quality of the raw water. When turbidity is 5 NTU or greater and/or total suspended solids are greater than 10 ppm, pre-filtration of the water is highly recommended.  Normally, it is advisable to install a 5 to 20 micron filter prior to a UV disinfection system.
 
Principles of UV Disinfection - Home Water Treatment

UV radiation has three wavelength zones: UV-A, UV-B, and UV-C, and it is this last region, the shortwave UV-C, that has germicidal properties for disinfection.  A low-pressure mercury arc lamp resembling a fluorescent lamp produces the UV light in the range of 254 manometers (nm).   A nm is one billionth of a meter (10^-9 meter). These lamps contain elemental mercury and an inert gas, such as argon, in a UV-transmitting tube, usually quartz. Traditionally, most mercury arc UV lamps have been the so-called "low pressure" type, because they operate at relatively low partial pressure of mercury, low overall vapor pressure (about 2 mbar), low external temperature (50-100oC) and low power. These lamps emit nearly monochromatic UV radiation at a wavelength of 254 nm, which is in the optimum range for UV energy absorption by nucleic acids (about 240-280 nm).

In recent years medium pressure UV lamps that operate at much higher pressures, temperatures and power levels and emit a broad spectrum of higher UV energy between 200 and 320 nm have become commercially available. However, for UV disinfection of home drinking water at the household level, the low-pressure lamps and systems are entirely adequate and even preferred to medium pressure lamps and systems. This is because they operate at lower power, lower temperature, and lower cost while being highly effective in disinfecting more than enough water for daily household use. An essential requirement for UV disinfection with lamp systems is an available and reliable source of electricity. While the power requirements of low-pressure mercury UV lamp disinfection systems are modest, they are essential for lamp operation to disinfect water. Since most microorganisms are affected by radiation around 260 nm, UV radiation is in the appropriate range for germicidal activity. There are UV lamps that produce radiation in the range of 185 nm that are effective on microorganisms and will also reduce the total organic carbon (TOC) content of the water.  For typical UV system, approximately 95 percent of the radiation passes through a quartz glass sleeve and into the untreated water.  The water is flowing as a thin film over the lamp.  The glass sleeve is designed to keep the lamp at an ideal temperature of approximately 104 °F. 
 
UV Radiation (How it Works)
UV radiation affects microorganisms by altering the DNA in the cells and impeding reproduction. UV treatment does not remove organisms from the water, it merely inactivates them. The effectiveness of this process is related to exposure time and lamp intensity as well as general water quality parameters.  The exposure time is reported as "microwatt-seconds per square centimeter" (uwatt-sec/cm^2), and the U.S. Department of Health and Human Services has established a minimum exposure of 16,000 µwatt-sec/cm^2 for UV disinfection systems.  Most manufacturers provide a lamp intensity of 30,000-50,000µwatt-sec/cm^2.  In general, coliform bacteria, for example, are destroyed at 7,000 µwatt-sec/cm^2.  Since lamp intensity decreases over time with use, lamp replacement and proper pretreatment are key to the success of  UV disinfection. In addition, UV systems should be equipped with a warning device to alert the owner when lamp intensity falls below the germicidal range.   The following gives the irradiation time required to inactivate completely various microorganisms under 30,000 µwatt-sec/cm^2 dose of UV 254 nm

Used alone, UV radiation does not improve the taste, odor, or clarity of water. UV light is a very effective disinfectant, although the disinfection can only occur inside the unit. There is no residual disinfection in the water to inactivate bacteria that may survive or may be introduced after the water passes by the light source. The percentage of microorganisms destroyed depends on the intensity of the UV light,  the contact time, raw water quality, and proper maintenance of the equipment.  If material builds up on the glass sleeve or the particle load is high, the light intensity and the effectiveness of treatment are reduced.  At sufficiently high doses, all waterborne enteric pathogens are inactivated by UV radiation. The general order of microbial resistance (from least to most) and corresponding UV doses for extensive (>99.9%) inactivation are: vegetative bacteria and the protozoan parasites Cryptosporidium parvum and Giardia lamblia at low doses (1-10 mJ/cm2) and enteric viruses and bacterial spores at high doses (30-150 mJ/cm2). Most low-pressure mercury lamp UV disinfection systems can readily achieve UV radiation doses of 50-150 mJ/cm2 in high quality water, and therefore efficiently disinfect essentially all waterborne pathogens. However, dissolved organic matter, such as natural organic matter, certain inorganic solutes, such as iron, sulfites and nitrites, and suspended matter (particulates or turbidity) will absorb UV radiation or shield microbes from UV radiation, resulting in lower delivered UV doses and reduced microbial disinfection. Another concern about disinfecting microbes with lower doses of UV radiation is the ability of bacteria and other cellular microbes to repair UV-induced damage and restore infectivity, a phenomenon known as reactivation. 

UV inactivates microbes primarily by chemically altering nucleic acids. However, the UV-induced chemical lesions can be repaired by cellular enzymatic mechanisms, some of which are independent of light (dark repair) and others of which require visible light (photorepair or photoreactivation). Therefore, achieving optimum UV disinfection of water requires delivering a sufficient UV dose to induce greater levels of nucleic acid damage and thereby overcome or overwhelm DNA repair mechanisms.

 

Table 1. Estimated Irradiation Time to 
Inactivate Microorganisms at a 
Dosage of 30,000 µwatt-sec/cm^2 of UV 254 nm

 

 

Name 100% lethal Dosage
(Second)
Name 100% lethal Dosage
(Second)
Bacteria
Dysentery bacilli 0.15 Micrococcus Candidus 0.4 ¨C 1.53
Leptospira SPP 0.2 Salmonella Paratyphi 0.41
Legionella Pneumophila 0.2 Mycobacterium Tuberculosis 0.41
Corynebacterium Diphtheriae 0.25 Streptococcus Haemolyticus 0.45
Shigella Dysenteriae 0.28 Salmonella Enteritidis 0.51
Bacillus Anthracis 0.3 Salmonella Typhimurium 0.53
Clostridium Tetani 0.33 Vibrio Cholerae 0.64
Escherichia coli 0.36 Clostridium Tetani 0.8
Pseudomonas Aeruginosa 0.37 Staphylococcus Albus 1.23
Virus
Coxsackie Virus A9 0.08 Echovirus 1 0.73
Adenovirus 3 0.1 Hepatitis B Virus 0.73
Bacteiophage 0.2 Echovirus 11 0.75
Influenza 0.23 Poliovirus 1 0.8
Rotavirus SA 11 0.52 Tobacco Mosaic 16
Mold Spores
Mucor Mucedo 0.23 ¨C 4.67 Penicillium Roqueforti 0.87 - 2.93
Oospara Lactis 0.33 Penicillium Chrysogenum 2.0 ¨C 3.33
Aspergillus Amstelodami 0.73 ¨C 8.80 Aspergillus Niger 6.67
Penicillium Digitatum 0.87 Manure Fungi 8
Algae
Chlorella Vulgaris 0.93 Protozoa 4 - 6.70
Green Algae 1.22 Paramecium 7.3
Nematode Eggs 3.4 Blue-Green Algae 10 ¨C 40
 

Inactivation Doses for Giardia and Cryptosporidium
UV dose is a product of UV light intensity and exposure time in seconds (IT), stated in units; mWs/cm2 or mJ/cm2. IT is analogous to the chemical dose or CT (concentration x time). Microbes show a range of sensitivities to UV as shown by the UV data. Cryptosporidium and Giardia are more sensitive to UV than bacteria and viruses are more resistant than bacteria. Similar results have been obtained using low-pressure, medium-pressure and pulsed UV irradiation- Look for a Class A UV disinfection system. UV dose required for a 4log inactivation of selected waterborne pathogens.

Table 2 .
UV Dose 4 log Inactivation
 

Pathogen UV dose mJcm/2
4log inactivation
Cryptosporidium parvum oocysts <10
Giardia lamblia cysts <10
Vibrio cholerae 2.9
Salmonella typhi 8.2
Shigella sonnei 8.2
Hepatitis A virus 30
Poliovirus Type 1 30
Rotavirus SA11 36

 Source: http://www.trojanuvmax.com

UV Irradiation Pretreatment
Either sediment filtration or activated carbon filtration should take place before water passes through the unit. Particulate matter, color, and turbidity affect the transmission of light to the microorganisms and must be removed for successful disinfection. 


Table 3. Recommended maximum contaminant 
levels in water entering a UV treatment device.

 

Turbidity 5 FTU or 5 NTU
Suspended solids
(5 to 10 micron prefiltration recommended)
< 10 mg/L
Color None
Iron < 0.3 mg/L
Manganese < 0.05 mg/L
pH 6.5-9.5

 

 

UV is often the last device in a treatment train (a series of treatment devices), following reverse osmosis, water softening, or filtration. The UV unit should be located as close as possible to the point-of-use since any part of the plumbing system could be contaminated with bacteria. It is recommended that the entire plumbing system be disinfected with chlorine prior to initial use of a UV system. 
 
Types of UV Disinfection Devices A Final Barrier

The typical UV treatment device consists, of a cylindrical chamber housing the UV bulb along its central axis. A quartz glass sleeve encases the bulb; water flow is parallel to the bulb, which requires electrical power. A flow control device prevents the water from passing too quickly past the bulb, assuring appropriate radiation contact time with the flowing water. It has been reported that turbulent (agitated) water flow provides more complete exposure of the organism to UV radiation. 

A UV system housing should be of stainless steel to protect any electronic parts from corrosion. To assure they will be contaminant-free, all welds in the system should be plasma-fused and purged with argon gas. The major differences in UV treatment units are in capacity and optional features. Some are equipped with UV emission detectors that warn the user when the unit needs cleaning or when the light source is failing. This feature is extremely important to assurance of a safe water supply. A detector that emits a sound or shuts off the water flow is preferable to a warning light, especially if the system might be located where a warning light would not be noticed immediately. 

Maintenance of a UV System

Since UV radiation must reach the bacteria to inactivate them, the housing for the light source must be kept clean. Commercial products are available for rinsing the unit to remove any film on the light source. An overnight cleaning with a solution of 0.15 percent sodium hydrosulfite or citric acid effectively removes such films. Some units have wipers to aid the cleaning process. 

UV systems are designed for continuous operation and should be shut down only if treatment is not needed for several days. A few minutes for lamp warm-up is needed before the system is used again following shut-down. In addition, the plumbing system of the house should be thoroughly flushed following a period of no use. Whenever the system is serviced, the entire plumbing system should be disinfected with a chemical such as chlorine prior to relying on the UV system for disinfection. 

UV lights gradually lose effectiveness with use, the lamp should be cleaned on a regular basis and replaced at least once a year. It is not uncommon for a new lamp to lose 20 percent of its intensity within the first 100 hours of operation, although that level is maintained for the next several thousand hours. As stated previously, units equipped with properly calibrated UV emission detectors alert the owner when the light intensity falls below a certain level. 

The treated water should be monitored for coliform and heterotrophic bacteria on a monthly basis for at least the first 6 months of the device’s use. If these organisms are present in the treated water, the lamp intensity should be checked, and the entire plumbing system should be disinfected with a chemical such as chlorine.
 

Quick Facts about UV Water Treatment
 

1. UV disinfection does not add chemicals to the water. 
2. UV is effective against bacteria and viruses; and may be effective against Giardia lamblia or Cryptosporidium if the system custom designed to meet these disinfection requirements.
3. UV disinfection has no residual disinfection. 
4. Minimum lamp exposure of 16,000 µwatt-sec / cm^2 . 
5. UV often last device in a treatment train of water treatment devices.
6. UV device should have audible UV emission detector to notify user when lamp intensity is inadequate. 
7. Regular maintenance and lamp replacement is essential.

Capacity of UV Disinfection Systems

UV is an in-line, point-of-entry system that treats all the water used in the house. The capacities range from 0.5 gallons per minute (gpm) to several hundred gpm.  Since bacteria may be shielded by particles in the water, pretreatment to remove turbidity may be required. There is also a limit to the number of bacteria that can be treated. An upper limit for UV disinfection is 1,000 total coliform/100 mL water or 100 fecal coliform/100 mL. 

Special Considerations

Prefiltration is required to remove color, turbidity, and particles that shield microorganisms from the UV source. Water that contains high mineral levels can coat the lamp sleeve and reduce the treatment effectiveness. Therefore, pretreatment with a water softener or phosphate injection system may be necessary to prevent build-up of minerals on the lamp. Table 3 lists the maximum levels of certain contaminants that are allowable for effective UV treatment. 

Overall Recommendations

Installing an UV treatment system, or any other water disinfection system is not a substitute for proper well design and construction.  If you have a dug well as a supply source, replacing the well is probably a more satisfactory long-term option. If a dug well or spring is your only supply option then look at all the treatment options before you decide what to do. Make sure you get advice from an expert!  Recommended treatment process selection:
1. Obtain information about your water source.
2. Get your water tested - At least Annually  
3. Determine which problems are associated with infrastructure deficiencies, i.e., cracked casing, no cap, improper seal, poor surface drainage, etc.  Make the necessary repairs and improvements to the system.
4. Install the necessary drinking water treatment systems.  I have provided some online links for water treatment systems, but I always recommend a preliminary water test.  

Calculating NSF Water Quality Index (WQI)

teachers, learning WQI, Act 48, stream, environmental education
Teachers Using Our Web Portal Via Distance Learning in 2014 
(This Portal Part of the Keystone Clean Water Team Efforts)

Current Sponsors for This Portal (Sponsors Needed):

B.F. Environmental Consultants Inc.
Water Testing Kits - Do It Yourself at Home !
Commercial Filtration Supply (Official Industrial Distributor) *
(*New Sponsor)
Know Your H20?  Neighborhood Hazard Surveys


Water quality index is a 100-point scale that summarizes results from a total of nine different measurements when complete:


 

Using the book Field Manual for Water Quality Monitoring, the National Sanitation Foundation surveyed 142 people representing a wide range of positions at the local, state, and national level about 35 water quality tests for possible inclusion in an index. Nine factors were chosen and some were judged more important than others, so a weighted mean is used to combine the values.

So that field measurements could be converted to index values, respondents were asked by questionnaire to graph the level of water quality (0 through 100) corresponding to the field measurements (e.g., pH 2-12). The curves were then averaged and are thought to represent the best professional judgment.  The updated calculator allows you to enter the latitude and longitude for the site or pick this location from the Google Earth Map.  The calculator completes the individual and group calculation and permits you to generate a customized report.  (Please like and share this resource !)



 

Other Monitoring Resources for Private Well OwnersEducators,
Professionals, and Students
Training Courses for Professionals

More References Related to:
Alkalinity SpeciationCalculatorWQI Index- Consumer Support Group Online Calculators

T
emperature Only
http://www.csgnetwork.com/h2oqualindexcvttemponlycalc.html

Path Finder Science
http://pathfinderscience.net/stream/cproto4.cfm

Water Quality Index Stream Monitoring Program
http://www.ecy.wa.gov/pubs/0203052.pdf

Back to Main Watershed Page

 

spring, fracking contamination, methane gas migration, SWIP, bacteria, spring
Boil Water Advisories - Surface Water Treatment Rule - GWUDI
 


 

Chlorine is the primary disinfectant used in the United States. In order to be effective, the chlorine must be given time to react with the microorganisms.

The time required depends on the temperature and the pH of the water. Chlorine works best in water with a low pH and a high temperature. The concentration and contact time required to inactivate Giardia using chlorine is approximated by the following formula.
 



CT=.2828 * ( pH^2.69 ) * ( Cl^.15 ) * (.933^(T-5)) * L
 


  •  
  • CT = Product of Free Chlorine Residual and Time required
  • pH = pH of water
  • Cl = Free Chlorine residual, mg/l
  • T = Temperature, degrees C
  • L = Log Removal
  •  

The PDFs below use this formula to solve for any desired parameter.
- CT Made Simple
- CT Lookup Table

Viruses

The CT concept was developed specifically for surfacewater, with the assumption that water suppliers would be trying to inactivate both Giardia and viruses. Since the CT required to provide 3 log inactivation of Giardia is at least enough to provide the required 4 log inactivation of viruses, the EPA just set the standard for Giardia and ignored viruses.

If a well tests positive for e. coli bacteria, it is very likely that it will test positive for viruses as well.  It seems reasonable, therefore, that the disinfection of a well that tests positive for coliform bacteria should be effective in inactivating viruses.

Just in case the Applet is not working - Here is a summary table with some inactivation and CT data as a function of pH, chlorine concentration, and log inactivations.
 


 

Water pH 6.0 at 0.5 C

Chlorine Conc  1.0 log 2.0 log 3.0 log 
0.4 mg/L 46 (CT value) 91 137
1.0 mg/L 49 99 148
2.0 mg/L 55 110 165

Water pH 7.0 at 0.5 C

Chlorine Conc 

1.0 log

2.0 log

3.0 log 

0.4 mg/L

65 (CT value)

130

195

1.0 mg/L

70

140

210

2.0 mg/L

79

157

236

 


Water pH 8.0 at 0.5 C

Chlorine Conc 

1.0 log

2.0 log

3.0 log 

0.4 mg/L

92 (CT value)

185

277

1.0 mg/L

101

203

304

2.0 mg/L

115

231

346

 



The next question is how do know how much contact time you are providing? 

Unfortunately, it is not as easy as dividing the storage volume by the flow rate. In order to count at all, there must be a separate inlet and outlet to the tank, widely separated. Even with this provided, the volume would then be discounted by one of the following baffling factors.

 

Baffling Condition Factor Description
Unbaffled 0.1 No baffling, low length to width ratio. Also applies to agitated basins (e.g. flocculation tanks)
Poor 0.3 unbaffled inlet/outlet. No baffles inside basin.
Average 0.5 Baffled inlet or outlet. Some inter-basin baffles.
Superior 0.7 Baffled inlet and outlet, serpentine inter-basin baffles.
Excellent 0.9 As above. Very high length-to-width ratio.
Perfect 
(plug Flow)
1.0 Used for pipe flow


Shock Well Disinfection Protocols

Water Quality Help Guides
Glossary of Water Terminology
Cryptosporidium Website

EPA Enhanced Surface Water Treatment Rule - EPA

 



Note: (This formula was provided by Peter Martin, an associate Engineer with the Contra Costa Water District, and was published in the AWWA Journal AWWA 85:12:12 Dec 1993).The applet above uses this formula to solve for any desired parameter. The applet may not be conservative for high pH, high chlorine residuals, and high temperatues.

 


 

Other Off-site Links

Water Treatment Systems- Residential and Commercial
Certified Water Testing Services
Professional Continuing Education Program and
B.F. Environmental Consultants Inc.
 

Surface Water Filtration and Groundwater Under the Influence Investigations


contaminated spring water, bottled water, groundwater under the influence, microscopic particulate analysis   direct filtration, pilot filter testing evaluation, slow sand filters, diatomaceous earth, pall filter, cartridge filters

Continuing Education Courses for Professional Engineers
 


During the past 15 years giardiasis and cryptosproridiosis has been recognized as one of the most frequently occurring waterborne diseases in the United States.

The occurrence and detection of this parasite and drinking water source identification and protection has become a matter of urgent concern to those responsible for water utility operation in endemic areas.   Because of these concerns the Surface Water Filtration Rule was established and protocols were developed for determining if a source was characterized as surface water, groundwater, or groundwater under the influence of source water. As part of the Surface Water Filtration Rule all community water supplies identified as surface water require a minimum of filtration rather than just disinfection prior to consumption. The Surface Water Filtration Rule has lead to the development of a protocol to evaluate the performance of filtration plants. The protocol is similar to the method used for the Groundwater Under the Influence Investigations, except the risk rankings and interpretations are based on a combination of the system configuration, source water quality, degree of particle reduction, and distribution of particles.

Since as the Director for the Center for Environmental Quality has conducted research in pilot filtration plant performance and optimization, the laboratory has been involved in the evaluation of a number of bench-scale, pilot, and full-scale filtration plants in Pennsylvania, New York, and New Jersey.   The laboratory Director has worked on projects using diatomaceous earth filtration, slow sand filtration, direct filtration, submicron filters, cartridge filters and upflow filtration systems.   In addition, we have conducted bench scale and pilot scale experiments to assist in optimization of pretreatment process and filtration of water supplies and has developed protocols and conducting testing to assist in the development of solid flux loadings for secondary clarifiers for a wastewater applications and living filtration systems for on-site wastewater disposal systems.
 

Microscopic Evaluation Technique for Filtration Plant Performance
 

The purpose of this procedure is to evaluate the performance of public water supply filtration systems. A minimum of 300 gallons of both raw and finished water should be collected. The evaluation is based on the filtration plants ability to remove Giardia sized and larger particles. In addition to the MET evaluation, the evaluator should also consider the operational conditions of the plant, physical condition of the plant/ raw water, and effluent quality of the finished water.

Each analysis culminates in a filtration performance rating which reflects the overall effluent quality. The rating is always accompanied by an explanation which details the justification of the assessment. Filtration Plants with Excellent and Good ratings are reported as "Acceptable Filtration Performance". Filter which are rated Questionable or Poor are reported as "Unacceptable Filtration Performance".

The amounts of each of several specific groups of particulate matter and microorganisms are recorded. These groups include: small particulate debris, large particulate debris, cellular plant debris, diatoms, and other algae, protozoa, insects and crustaceans, nematodes, and rotifers. Also, pollen grains, Giardia, and other parasitic protozoa should be noted.
 



No of Specific Particles in a Category
Avg. Field at 100x

None  0
Rare  1 - 50
++  Few  51 - 100
++++ Moderate > 200

 



Excellent- These systems remove essentially all of the Giardia sized debris and that which is much smaller. There is no evidence of turbidity breakthrough to indicate any risk for Giardia contamination of the effluent and 300 gallons of effluent can be observed in a single sample without any Giardia sized particles reaching the rare level (+).

Good-300 gallons of effluent can be observed in a single subsample without significant amounts of Giardia sized particles present, i.e., the levels of diatoms, algae, and protozoa remain a the few (++) level.

Questionable-Giardia sized particles are at the moderate (+++) level in samples which represent 300 gallons of effluent. These systems have filtration which does not provide the obvious assurance for Giardia removal as in the above two ratings. It is not possible to comfortably predict the potential for Giardia breakthrough with this result.  Facility evaluations rely heavily on information obtained in the operations survey.

Poor-These systems are unable to remove Giardia sized particles and are therefore vulnerable for Giardia passage through the facility. Subsamples represent 300 gallons of effluent, and Giardia sized debris is in the moderated (+++) to many (++++) range. Operational changes are required to improve the effluent quality. The facility must be reevaluated to determine whether correction of the problem was achieved. Corrections must be performed within a reasonable time period and public notified if the potential for Giardia contamination remains.
 



Advanced Stormwater Design

Chlorination of Drinking Water
Private Well Owner and Small System Operator Guide


chlorination, disinfection
Commercial System
DIY - Bacterial Screening Test

 

Recent Sponsors for this Portal 
B.F. Environmental Consultants Inc.
Water Testing Kits - Do It Yourself at Home !
Crystal Quest Disinfection Systems (Official Industrial Distributor) *
(*New Sponsor)


 

Water used for drinking and cooking should be free of pathogenic (disease causing) microorganisms that cause such illnesses as typhoid fever, dysentery, cholera, and gastroenteritis.

Whether a person contracts these diseases from water depends on the type of pathogen, the number of organisms in the water (density), the strength of the organism (virulence), the volume of water ingested, and the susceptibility of the individual. Purification of drinking water containing pathogenic microorganisms requires specific treatment called disinfection.

Although several methods eliminate disease-causing microorganisms in water, chlorination is the most commonly used. Chlorination is effective against many pathogenic bacteria, but at normal dosage rates it does not kill all viruses, cysts, or worms. When combined with filtration, chlorination is an excellent way to disinfect drinking water supplies.


This fact sheet discusses the requirements of a disinfection system, how to test the biological quality of drinking water, how to calculate the amount of chlorine needed in a particular situation, chlorination equipment, by-products of disinfection, and alternative disinfection methods.   A new pathogen screening test is Now Available.


Disinfection requirements

Disinfection reduces pathogenic microorganisms in the water to levels designated safe by public health standards. This prevents the transmission of disease.

An effective disinfection system kills or neutralizes all pathogens in the water. It is automatic, simply maintained, safe, and inexpensive. An ideal system treats all the water and provides residual (long term) disinfection. Chemicals should be easily stored and not make the water unpalatable.  State and federal governments require public water supplies to be biologically safe.

The U.S. Environmental Protection Agency (EPA) recently proposed expanded regulations to increase the protection provided by public water systems. Water supply operators will be directed to disinfect and, if necessary, filter the water to prevent contamination from Giardia lamblia, coliform bacteria, viruses, heterotrophic bacteria, turbidity, and Legionella.

Private systems, while not federally regulated, also are vulnerable to biological contamination from sewage, improper well construction, and poor-quality water sources. Since more than 30 million people in the United States rely on private wells for drinking water, maintaining biologically safe water is a major concern.


Testing water for biological quality

The biological quality of drinking water is determined by tests for coliform group bacteria. These organisms are found in the intestinal tract of warm-blooded animals and in the soil. Their presence in water indicates pathogenic contamination, but they are not considered to be pathogens. The standard for coliform bacteria in drinking water is "less than 1 coliform colony per 100 milliliters of sample" (< 1/ 100ml).

Public water systems are required to test regularly for coliform bacteria. Private system testing is done at the owner's discretion. Drinking water from a private system should be tested for biological quality at least once each year, usually in the spring. Testing is also recommended following repair or improvements in the well.

Coliform presence in a water sample does not necessarily mean that the water is hazardous to drink. The test is a screening technique, and a positive result (more than 1 colony per 100 ml water sample) means the water should be retested. The retested sample should be analyzed for fecal coliform organisms. A high positive test result, however, indicates substantial contamination requiring prompt action. Such water should not be consumed until the source of contamination is determined and the water purified.

A  testing laboratory provides specific sampling instructions and containers. The sampling protocol includes the following:

run cold water for a few minutes (15 minutes) to clear the lines;

use sterile sample container and handle only the outside of container and cap; and

upon collecting the sample, immediately cap bottle and place in a chilled container if delivery to lab exceeds 1 hour (never exceed 30 hours). Many laboratories do not accept samples on Friday due to time limits.


Chlorine treatment

Chlorine readily combines with chemicals dissolved in water, microorganisms, small animals, plant material, tastes, odors, and colors. These components "use up" chlorine and comprise the chlorine demand of the treatment system. It is important to add sufficient chlorine to the water to meet the chlorine demand and provide residual disinfection.

The chlorine that does not combine with other components in the water is free (residual) chlorine, and the breakpoint is the point at which free chlorine is available for continuous disinfection. An ideal system supplies free chlorine at a concentration of 0.3-0.5 mg/l. Simple test kits, most commonly the DPD colorimetric test kit (so called because diethyl phenylene diamine produces the color reaction), are available for testing breakpoint and chlorine residual in private systems. The kit must test free chlorine, not total chlorine.  We also recommend monitoring the ORP (Oxidation Reduction Potential) of the water.  Paper - Use of ORP Monitoring for Disinfection  University of California and YSI.


Contact time with microorganisms

The contact (retention) time (Table 1) in chlorination is that period between the introduction of the disinfectant and when the water is used. A long interaction between chlorine and the microorganisms results in an effective disinfection process. The contact time varies with chlorine concentration, the type of pathogens present, pH, and temperature of the water. The calculation procedure is given below.

Contact time must increase under conditions of low water temperature or high pH (alkalinity). Complete mixing of chlorine and water is necessary, and often a holding tank is needed to achieve appropriate contact time. In a private well system, the minimum-size holding tank is determined by multiplying the capacity of the pump by 10. For example, a 5-gallons-per-minute (GPM) pump requires a 50-gallon holding tank. Pressure tanks are not recommended for this purpose since they usually have a combined inlet/outlet and all the water does not pass through the tank.

An alternative to the holding tank is a long length of coiled pipe to increase contact between water and chlorine. Scaling and sediment build-up inside the pipe make this method inferior to the holding tank.
 


 

Table 1. Calculating Contact Time

minutes required = K / chlorine residual (mg/l)
 

K values to determine chlorine contact time


Highest

 

Lowest Water Temperature (degrees F)

 

pH

> 50

45

< 40


6.5

4

5

6

7.0

8

10

12

7.5

12

15

18

8.0

16

20

24

8.5

20

25

30

9.0

24

30

36



To calculate contact time, one should use the highest pH and lowest water temperature expected. For example, if the highest pH anticipated is 7.5 and the lowest water temperature is 42 °F, the "K" value (from the table below) to use in the formula is 15. Therefore, a chlorine residual of 0.5 mg/l necessitates 30 minutes contact time. A residual of 0.3 mg/l requires 50 minutes contact time for adequate disinfection.

 

Chlorination levels

If a system does not allow adequate contact time with normal dosages of chlorine, superchlorination followed by dechlorination (chlorine removal) may be necessary.

Superchlorination provides a chlorine residual of 3.0-5.0 mg/l, 10 times the recommended minimum breakpoint chlorine concentration. Retention time for superchlorination is approximately 5 minutes. Activated carbon filtration removes the high chlorine residual.

Shock chlorination is recommended whenever a well is new, repaired, or found to be contaminated. This treatment introduces high levels of chlorine to the water. Unlike superchlorination, shock chlorination is a "one time only" occurrence, and chlorine is depleted as water flows through the system; activated carbon treatment is not required. If bacteriological problems persist following shock chlorination, the system should be evaluated.  More information regarding shock disinfection can be found at Shock Well Disinfection Website. 

 



CHLORINATION GUIDELINES

Chlorine solutions lose strength while standing or when exposed to air or sunlight. Make fresh solutions frequently to maintain the necessary residual.

Maintain a free chlorine residual of 0.3-0.5 mg/l after a 10-minute contact time. Measure the residual frequently.

Once the chlorine dosage is increased to meet greater demand, do not decrease it.

Locate and eliminate the source of contamination to avoid continuous chlorination. If a water source is available that does not require disinfection, use it.

Keep records of pertinent information concerning the chlorination system and we recommend that you monitor the ORP of the water.


Types of chlorine used in disinfection

Public water systems use chlorine in the gaseous form, which is considered too dangerous and expensive for home use. Private systems use liquid chlorine (sodium hypochlorite) or dry chlorine (calcium hypochlorite). To avoid hardness deposits on equipment, manufacturers recommend using soft, distilled, or demineralized water when making up chlorine solutions.

 

Liquid Chlorine
    •  
    • household bleach most common form
    • available chlorine range: 
 
    • 5.25% (domestic laundry bleach) 
 
  • 18% (commercial laundry bleach)
  • slightly more stable than solutions from dry chlorine
  • protect from sun, air, and heat
Dry Chlorine
  •  
  • powder dissolved in water
  • available chlorine: 4%
  • produces heavy sediment that clogs equipment; filtration required
  • dry powder stable when stored properly
  • dry powder fire hazard near flammable materials
  • solution maintains strength for 1 week
  • protect from sun and heat

 

Equipment for continuous chlorination

Continuous chlorination of a private water supply can be done by various methods. The injection device should operate only when water is being pumped, and the water pump should shut off if the chlorinator fails or if the chlorine supply is depleted. A brief description of common chlorination devices follows.
 

chlorine pump (see Fig. 1):

  • commonly used, positive displacement or chemical-feed device,
  • adds a small amount, of chlorine to the water,
  • dose either fixed or varies with water flow rates
  • recommended for low and fluctuating water pressure,
  • chlorine drawn into the device then pumped to water delivery line

 

chlorination diagrams

Figure 1. Pump type (positive displacement) chlorinator

Figure 2. Injector (aspirator) chlorinator
 



suction device:

  • The line from chlorine supply to the suction side of water pump,
  • chlorine drawn into the water held in the well pump,
  • dosage uniformity not assured with this system,
  • some suction devices inject chlorine directly into well water, increasing the contact time between microorganisms and disinfectant; water/chlorine mixture is then drawn into the well pump


aspirator (see Fig. 2):

  • simple, inexpensive mechanism,
  • requires no electricity,
  • the vacuum created by water flowing through a tube draws chlorine into a tank where it mixes with untreated water,
  • treated solution fed into the water system,
  • chlorine doses not consistently accurate


solid feed unit:

  • waste treatment and swimming pool disinfection,
  • requires no electricity,
  • controlled by a flow meter,
  • the device slowly dissolves chlorine tablets to provide continuous supply of chlorine solution


batch disinfection:

  • used for fluctuating chlorine demand,
  • three tanks, each holding 2 to 3 days' water supply, alternately filled, treated and used


Disinfection by-products

Trihalomethanes (THMS) are chemicals that are formed, primarily in surface water, when naturally occurring organic materials (humic and fulvic acids from degradation of plant material) combine with free chlorine. Some of the THMs present in drinking water are chloroform, bromoform, and bromodichloromethane. Since groundwater rarely has high levels of humic and fulvic acids, chlorinated private wells contain much lower levels of these chemicals.

THMs are linked to increases in some cancers, but the potential for human exposure to THMs from drinking water varies with season, contact time, water temperature, pH, water chemistry and disinfection method. Although there is a risk from consuming THMs in chlorinated drinking water, the health hazards of undisinfected water are much greater. The primary standard (maximum contaminant level) for total THMs in drinking water is 0.10 mg/l, and activated carbon filtration removes THMs from water.   Our comprehensive water quality test kit for City Water or Well Water.

Important tools, Chlorine Monitoring and ORP Monitoring.
 

Other Outside Links
Community Environmental Hazard Reports

Water Treatment Systems- Residential and Commercial

Water Training Courses
Drinking Water Treatment
Water and Wastewater Design
Drilling Safety and Groundwater Basics 
Water Well Design

 

Calculating NSF Water Quality Index (WQI)

teachers, learning WQI, Act 48, stream, environmental education
Teachers Using Our Web Portal Via Distance Learning in 2014 
(This Portal Part of the Keystone Clean Water Team Efforts)

Current Sponsors for This Portal (Sponsors Needed):

B.F. Environmental Consultants Inc.
Water Testing Kits - Do It Yourself at Home !
Commercial Filtration Supply (Official Industrial Distributor) *
(*New Sponsor)
Know Your H20?  Neighborhood Hazard Surveys


Water quality index is a 100-point scale that summarizes results from a total of nine different measurements when complete:


 

Using the book Field Manual for Water Quality Monitoring, the National Sanitation Foundation surveyed 142 people representing a wide range of positions at the local, state, and national level about 35 water quality tests for possible inclusion in an index. Nine factors were chosen and some were judged more important than others, so a weighted mean is used to combine the values.

So that field measurements could be converted to index values, respondents were asked by questionnaire to graph the level of water quality (0 through 100) corresponding to the field measurements (e.g., pH 2-12). The curves were then averaged and are thought to represent the best professional judgment.  The updated calculator allows you to enter the latitude and longitude for the site or pick this location from the Google Earth Map.  The calculator completes the individual and group calculation and permits you to generate a customized report.  (Please like and share this resource !)



 

Other Monitoring Resources for Private Well OwnersEducators,
Professionals, and Students
Training Courses for Professionals

More References Related to:
Alkalinity SpeciationCalculatorWQI Index- Consumer Support Group Online Calculators

T
emperature Only
http://www.csgnetwork.com/h2oqualindexcvttemponlycalc.html

Path Finder Science
http://pathfinderscience.net/stream/cproto4.cfm

Water Quality Index Stream Monitoring Program
http://www.ecy.wa.gov/pubs/0203052.pdf

Back to Main Watershed Page

 

spring, fracking contamination, methane gas migration, SWIP, bacteria, spring
Boil Water Advisories - Surface Water Treatment Rule - GWUDI
 


 

Chlorine is the primary disinfectant used in the United States. In order to be effective, the chlorine must be given time to react with the microorganisms.

The time required depends on the temperature and the pH of the water. Chlorine works best in water with a low pH and a high temperature. The concentration and contact time required to inactivate Giardia using chlorine is approximated by the following formula.
 



CT=.2828 * ( pH^2.69 ) * ( Cl^.15 ) * (.933^(T-5)) * L
 


  •  
  • CT = Product of Free Chlorine Residual and Time required
  • pH = pH of water
  • Cl = Free Chlorine residual, mg/l
  • T = Temperature, degrees C
  • L = Log Removal
  •  

The PDFs below use this formula to solve for any desired parameter.
- CT Made Simple
- CT Lookup Table

Viruses

The CT concept was developed specifically for surfacewater, with the assumption that water suppliers would be trying to inactivate both Giardia and viruses. Since the CT required to provide 3 log inactivation of Giardia is at least enough to provide the required 4 log inactivation of viruses, the EPA just set the standard for Giardia and ignored viruses.

If a well tests positive for e. coli bacteria, it is very likely that it will test positive for viruses as well.  It seems reasonable, therefore, that the disinfection of a well that tests positive for coliform bacteria should be effective in inactivating viruses.

Just in case the Applet is not working - Here is a summary table with some inactivation and CT data as a function of pH, chlorine concentration, and log inactivations.
 


 

Water pH 6.0 at 0.5 C

Chlorine Conc  1.0 log 2.0 log 3.0 log 
0.4 mg/L 46 (CT value) 91 137
1.0 mg/L 49 99 148
2.0 mg/L 55 110 165

Water pH 7.0 at 0.5 C

Chlorine Conc 

1.0 log

2.0 log

3.0 log 

0.4 mg/L

65 (CT value)

130

195

1.0 mg/L

70

140

210

2.0 mg/L

79

157

236

 


Water pH 8.0 at 0.5 C

Chlorine Conc 

1.0 log

2.0 log

3.0 log 

0.4 mg/L

92 (CT value)

185

277

1.0 mg/L

101

203

304

2.0 mg/L

115

231

346

 



The next question is how do know how much contact time you are providing? 

Unfortunately, it is not as easy as dividing the storage volume by the flow rate. In order to count at all, there must be a separate inlet and outlet to the tank, widely separated. Even with this provided, the volume would then be discounted by one of the following baffling factors.

 

Baffling Condition Factor Description
Unbaffled 0.1 No baffling, low length to width ratio. Also applies to agitated basins (e.g. flocculation tanks)
Poor 0.3 unbaffled inlet/outlet. No baffles inside basin.
Average 0.5 Baffled inlet or outlet. Some inter-basin baffles.
Superior 0.7 Baffled inlet and outlet, serpentine inter-basin baffles.
Excellent 0.9 As above. Very high length-to-width ratio.
Perfect 
(plug Flow)
1.0 Used for pipe flow


Shock Well Disinfection Protocols

Water Quality Help Guides
Glossary of Water Terminology
Cryptosporidium Website

EPA Enhanced Surface Water Treatment Rule - EPA

 



Note: (This formula was provided by Peter Martin, an associate Engineer with the Contra Costa Water District, and was published in the AWWA Journal AWWA 85:12:12 Dec 1993).The applet above uses this formula to solve for any desired parameter. The applet may not be conservative for high pH, high chlorine residuals, and high temperatues.

 


 

Other Off-site Links

Water Treatment Systems- Residential and Commercial
Certified Water Testing Services
Professional Continuing Education Program and
B.F. Environmental Consultants Inc.
 

Surface Water Filtration and Groundwater Under the Influence Investigations


contaminated spring water, bottled water, groundwater under the influence, microscopic particulate analysis   direct filtration, pilot filter testing evaluation, slow sand filters, diatomaceous earth, pall filter, cartridge filters

Continuing Education Courses for Professional Engineers
 


During the past 15 years giardiasis and cryptosproridiosis has been recognized as one of the most frequently occurring waterborne diseases in the United States.

The occurrence and detection of this parasite and drinking water source identification and protection has become a matter of urgent concern to those responsible for water utility operation in endemic areas.   Because of these concerns the Surface Water Filtration Rule was established and protocols were developed for determining if a source was characterized as surface water, groundwater, or groundwater under the influence of source water. As part of the Surface Water Filtration Rule all community water supplies identified as surface water require a minimum of filtration rather than just disinfection prior to consumption. The Surface Water Filtration Rule has lead to the development of a protocol to evaluate the performance of filtration plants. The protocol is similar to the method used for the Groundwater Under the Influence Investigations, except the risk rankings and interpretations are based on a combination of the system configuration, source water quality, degree of particle reduction, and distribution of particles.

Since as the Director for the Center for Environmental Quality has conducted research in pilot filtration plant performance and optimization, the laboratory has been involved in the evaluation of a number of bench-scale, pilot, and full-scale filtration plants in Pennsylvania, New York, and New Jersey.   The laboratory Director has worked on projects using diatomaceous earth filtration, slow sand filtration, direct filtration, submicron filters, cartridge filters and upflow filtration systems.   In addition, we have conducted bench scale and pilot scale experiments to assist in optimization of pretreatment process and filtration of water supplies and has developed protocols and conducting testing to assist in the development of solid flux loadings for secondary clarifiers for a wastewater applications and living filtration systems for on-site wastewater disposal systems.
 

Microscopic Evaluation Technique for Filtration Plant Performance
 

The purpose of this procedure is to evaluate the performance of public water supply filtration systems. A minimum of 300 gallons of both raw and finished water should be collected. The evaluation is based on the filtration plants ability to remove Giardia sized and larger particles. In addition to the MET evaluation, the evaluator should also consider the operational conditions of the plant, physical condition of the plant/ raw water, and effluent quality of the finished water.

Each analysis culminates in a filtration performance rating which reflects the overall effluent quality. The rating is always accompanied by an explanation which details the justification of the assessment. Filtration Plants with Excellent and Good ratings are reported as "Acceptable Filtration Performance". Filter which are rated Questionable or Poor are reported as "Unacceptable Filtration Performance".

The amounts of each of several specific groups of particulate matter and microorganisms are recorded. These groups include: small particulate debris, large particulate debris, cellular plant debris, diatoms, and other algae, protozoa, insects and crustaceans, nematodes, and rotifers. Also, pollen grains, Giardia, and other parasitic protozoa should be noted.
 



No of Specific Particles in a Category
Avg. Field at 100x

None  0
Rare  1 - 50
++  Few  51 - 100
++++ Moderate > 200

 



Excellent- These systems remove essentially all of the Giardia sized debris and that which is much smaller. There is no evidence of turbidity breakthrough to indicate any risk for Giardia contamination of the effluent and 300 gallons of effluent can be observed in a single sample without any Giardia sized particles reaching the rare level (+).

Good-300 gallons of effluent can be observed in a single subsample without significant amounts of Giardia sized particles present, i.e., the levels of diatoms, algae, and protozoa remain a the few (++) level.

Questionable-Giardia sized particles are at the moderate (+++) level in samples which represent 300 gallons of effluent. These systems have filtration which does not provide the obvious assurance for Giardia removal as in the above two ratings. It is not possible to comfortably predict the potential for Giardia breakthrough with this result.  Facility evaluations rely heavily on information obtained in the operations survey.

Poor-These systems are unable to remove Giardia sized particles and are therefore vulnerable for Giardia passage through the facility. Subsamples represent 300 gallons of effluent, and Giardia sized debris is in the moderated (+++) to many (++++) range. Operational changes are required to improve the effluent quality. The facility must be reevaluated to determine whether correction of the problem was achieved. Corrections must be performed within a reasonable time period and public notified if the potential for Giardia contamination remains.
 



Advanced Stormwater Design

Chlorination of Drinking Water
Private Well Owner and Small System Operator Guide


chlorination, disinfection
Commercial System
DIY - Bacterial Screening Test

 

Recent Sponsors for this Portal 
B.F. Environmental Consultants Inc.
Water Testing Kits - Do It Yourself at Home !
Crystal Quest Disinfection Systems (Official Industrial Distributor) *
(*New Sponsor)


 

Water used for drinking and cooking should be free of pathogenic (disease causing) microorganisms that cause such illnesses as typhoid fever, dysentery, cholera, and gastroenteritis.

Whether a person contracts these diseases from water depends on the type of pathogen, the number of organisms in the water (density), the strength of the organism (virulence), the volume of water ingested, and the susceptibility of the individual. Purification of drinking water containing pathogenic microorganisms requires specific treatment called disinfection.

Although several methods eliminate disease-causing microorganisms in water, chlorination is the most commonly used. Chlorination is effective against many pathogenic bacteria, but at normal dosage rates it does not kill all viruses, cysts, or worms. When combined with filtration, chlorination is an excellent way to disinfect drinking water supplies.


This fact sheet discusses the requirements of a disinfection system, how to test the biological quality of drinking water, how to calculate the amount of chlorine needed in a particular situation, chlorination equipment, by-products of disinfection, and alternative disinfection methods.   A new pathogen screening test is Now Available.


Disinfection requirements

Disinfection reduces pathogenic microorganisms in the water to levels designated safe by public health standards. This prevents the transmission of disease.

An effective disinfection system kills or neutralizes all pathogens in the water. It is automatic, simply maintained, safe, and inexpensive. An ideal system treats all the water and provides residual (long term) disinfection. Chemicals should be easily stored and not make the water unpalatable.  State and federal governments require public water supplies to be biologically safe.

The U.S. Environmental Protection Agency (EPA) recently proposed expanded regulations to increase the protection provided by public water systems. Water supply operators will be directed to disinfect and, if necessary, filter the water to prevent contamination from Giardia lamblia, coliform bacteria, viruses, heterotrophic bacteria, turbidity, and Legionella.

Private systems, while not federally regulated, also are vulnerable to biological contamination from sewage, improper well construction, and poor-quality water sources. Since more than 30 million people in the United States rely on private wells for drinking water, maintaining biologically safe water is a major concern.


Testing water for biological quality

The biological quality of drinking water is determined by tests for coliform group bacteria. These organisms are found in the intestinal tract of warm-blooded animals and in the soil. Their presence in water indicates pathogenic contamination, but they are not considered to be pathogens. The standard for coliform bacteria in drinking water is "less than 1 coliform colony per 100 milliliters of sample" (< 1/ 100ml).

Public water systems are required to test regularly for coliform bacteria. Private system testing is done at the owner's discretion. Drinking water from a private system should be tested for biological quality at least once each year, usually in the spring. Testing is also recommended following repair or improvements in the well.

Coliform presence in a water sample does not necessarily mean that the water is hazardous to drink. The test is a screening technique, and a positive result (more than 1 colony per 100 ml water sample) means the water should be retested. The retested sample should be analyzed for fecal coliform organisms. A high positive test result, however, indicates substantial contamination requiring prompt action. Such water should not be consumed until the source of contamination is determined and the water purified.

A  testing laboratory provides specific sampling instructions and containers. The sampling protocol includes the following:

run cold water for a few minutes (15 minutes) to clear the lines;

use sterile sample container and handle only the outside of container and cap; and

upon collecting the sample, immediately cap bottle and place in a chilled container if delivery to lab exceeds 1 hour (never exceed 30 hours). Many laboratories do not accept samples on Friday due to time limits.


Chlorine treatment

Chlorine readily combines with chemicals dissolved in water, microorganisms, small animals, plant material, tastes, odors, and colors. These components "use up" chlorine and comprise the chlorine demand of the treatment system. It is important to add sufficient chlorine to the water to meet the chlorine demand and provide residual disinfection.

The chlorine that does not combine with other components in the water is free (residual) chlorine, and the breakpoint is the point at which free chlorine is available for continuous disinfection. An ideal system supplies free chlorine at a concentration of 0.3-0.5 mg/l. Simple test kits, most commonly the DPD colorimetric test kit (so called because diethyl phenylene diamine produces the color reaction), are available for testing breakpoint and chlorine residual in private systems. The kit must test free chlorine, not total chlorine.  We also recommend monitoring the ORP (Oxidation Reduction Potential) of the water.  Paper - Use of ORP Monitoring for Disinfection  University of California and YSI.


Contact time with microorganisms

The contact (retention) time (Table 1) in chlorination is that period between the introduction of the disinfectant and when the water is used. A long interaction between chlorine and the microorganisms results in an effective disinfection process. The contact time varies with chlorine concentration, the type of pathogens present, pH, and temperature of the water. The calculation procedure is given below.

Contact time must increase under conditions of low water temperature or high pH (alkalinity). Complete mixing of chlorine and water is necessary, and often a holding tank is needed to achieve appropriate contact time. In a private well system, the minimum-size holding tank is determined by multiplying the capacity of the pump by 10. For example, a 5-gallons-per-minute (GPM) pump requires a 50-gallon holding tank. Pressure tanks are not recommended for this purpose since they usually have a combined inlet/outlet and all the water does not pass through the tank.

An alternative to the holding tank is a long length of coiled pipe to increase contact between water and chlorine. Scaling and sediment build-up inside the pipe make this method inferior to the holding tank.
 


 

Table 1. Calculating Contact Time

minutes required = K / chlorine residual (mg/l)
 

K values to determine chlorine contact time


Highest

 

Lowest Water Temperature (degrees F)

 

pH

> 50

45

< 40


6.5

4

5

6

7.0

8

10

12

7.5

12

15

18

8.0

16

20

24

8.5

20

25

30

9.0

24

30

36



To calculate contact time, one should use the highest pH and lowest water temperature expected. For example, if the highest pH anticipated is 7.5 and the lowest water temperature is 42 °F, the "K" value (from the table below) to use in the formula is 15. Therefore, a chlorine residual of 0.5 mg/l necessitates 30 minutes contact time. A residual of 0.3 mg/l requires 50 minutes contact time for adequate disinfection.

 

Chlorination levels

If a system does not allow adequate contact time with normal dosages of chlorine, superchlorination followed by dechlorination (chlorine removal) may be necessary.

Superchlorination provides a chlorine residual of 3.0-5.0 mg/l, 10 times the recommended minimum breakpoint chlorine concentration. Retention time for superchlorination is approximately 5 minutes. Activated carbon filtration removes the high chlorine residual.

Shock chlorination is recommended whenever a well is new, repaired, or found to be contaminated. This treatment introduces high levels of chlorine to the water. Unlike superchlorination, shock chlorination is a "one time only" occurrence, and chlorine is depleted as water flows through the system; activated carbon treatment is not required. If bacteriological problems persist following shock chlorination, the system should be evaluated.  More information regarding shock disinfection can be found at Shock Well Disinfection Website. 

 



CHLORINATION GUIDELINES

Chlorine solutions lose strength while standing or when exposed to air or sunlight. Make fresh solutions frequently to maintain the necessary residual.

Maintain a free chlorine residual of 0.3-0.5 mg/l after a 10-minute contact time. Measure the residual frequently.

Once the chlorine dosage is increased to meet greater demand, do not decrease it.

Locate and eliminate the source of contamination to avoid continuous chlorination. If a water source is available that does not require disinfection, use it.

Keep records of pertinent information concerning the chlorination system and we recommend that you monitor the ORP of the water.


Types of chlorine used in disinfection

Public water systems use chlorine in the gaseous form, which is considered too dangerous and expensive for home use. Private systems use liquid chlorine (sodium hypochlorite) or dry chlorine (calcium hypochlorite). To avoid hardness deposits on equipment, manufacturers recommend using soft, distilled, or demineralized water when making up chlorine solutions.

 

Liquid Chlorine
    •  
    • household bleach most common form
    • available chlorine range: 
 
    • 5.25% (domestic laundry bleach) 
 
  • 18% (commercial laundry bleach)
  • slightly more stable than solutions from dry chlorine
  • protect from sun, air, and heat
Dry Chlorine
  •  
  • powder dissolved in water
  • available chlorine: 4%
  • produces heavy sediment that clogs equipment; filtration required
  • dry powder stable when stored properly
  • dry powder fire hazard near flammable materials
  • solution maintains strength for 1 week
  • protect from sun and heat

 

Equipment for continuous chlorination

Continuous chlorination of a private water supply can be done by various methods. The injection device should operate only when water is being pumped, and the water pump should shut off if the chlorinator fails or if the chlorine supply is depleted. A brief description of common chlorination devices follows.
 

chlorine pump (see Fig. 1):

  • commonly used, positive displacement or chemical-feed device,
  • adds a small amount, of chlorine to the water,
  • dose either fixed or varies with water flow rates
  • recommended for low and fluctuating water pressure,
  • chlorine drawn into the device then pumped to water delivery line

 

chlorination diagrams

Figure 1. Pump type (positive displacement) chlorinator

Figure 2. Injector (aspirator) chlorinator
 



suction device:

  • The line from chlorine supply to the suction side of water pump,
  • chlorine drawn into the water held in the well pump,
  • dosage uniformity not assured with this system,
  • some suction devices inject chlorine directly into well water, increasing the contact time between microorganisms and disinfectant; water/chlorine mixture is then drawn into the well pump


aspirator (see Fig. 2):

  • simple, inexpensive mechanism,
  • requires no electricity,
  • the vacuum created by water flowing through a tube draws chlorine into a tank where it mixes with untreated water,
  • treated solution fed into the water system,
  • chlorine doses not consistently accurate


solid feed unit:

  • waste treatment and swimming pool disinfection,
  • requires no electricity,
  • controlled by a flow meter,
  • the device slowly dissolves chlorine tablets to provide continuous supply of chlorine solution


batch disinfection:

  • used for fluctuating chlorine demand,
  • three tanks, each holding 2 to 3 days' water supply, alternately filled, treated and used


Disinfection by-products

Trihalomethanes (THMS) are chemicals that are formed, primarily in surface water, when naturally occurring organic materials (humic and fulvic acids from degradation of plant material) combine with free chlorine. Some of the THMs present in drinking water are chloroform, bromoform, and bromodichloromethane. Since groundwater rarely has high levels of humic and fulvic acids, chlorinated private wells contain much lower levels of these chemicals.

THMs are linked to increases in some cancers, but the potential for human exposure to THMs from drinking water varies with season, contact time, water temperature, pH, water chemistry and disinfection method. Although there is a risk from consuming THMs in chlorinated drinking water, the health hazards of undisinfected water are much greater. The primary standard (maximum contaminant level) for total THMs in drinking water is 0.10 mg/l, and activated carbon filtration removes THMs from water.   Our comprehensive water quality test kit for City Water or Well Water.

Important tools, Chlorine Monitoring and ORP Monitoring.
 

Other Outside Links
Community Environmental Hazard Reports

Water Treatment Systems- Residential and Commercial

Water Training Courses
Drinking Water Treatment
Water and Wastewater Design
Drilling Safety and Groundwater Basics 
Water Well Design

 

Know Your H2O? Mobile App

Join Our Newsletter

Sign Up to Receive
Our FREE Newsletter for
the Latest News & Information

New Booklet

Order Your Copy of the PA Water Quality Guide

Covers issues related to water conservation, the sources of pollution, ensuring that private water supply systems produce safe drinking water and protecting the long-term quality of our water sources.

Order

Support

Support this Portal and Outreach

Our Current Sponsors

Water Research Center

Surveys

Resources

...In Drinking Water

/C MID -->